7.2/12kV 2 Tier Metal-enclosed Switchgear Type MS-E
Features
1. Structure
- The operability, serviceability and maintainability of machinery have been improved by arranging components used frequently, such as the drawer-type devices (e.g., VPR/VMC/VT units), grounding switchgear, and monitor and control devices, in a compartment on the front of the panel front, and protective devices (e.g., CT, ZCT, LA, and CR) and the main circuit cable in a compartment on the back of the panel.
2. Specifications
- The MS-E can operate up to a maximum busbar current rating of 3,150A using natural ventilation.
- The incorporation of a (FBC) epoxy resin coating (FBC) having a long history of good performance when used between main circuit phases and ground connections, provides even stronger insulation for the live sections of the main circuit. (optional)
- The drawer-type VPR/VMC units built into the MS-E offer the highest mechanical durability and electronic durability classifications, and comply with IEC international standards.
・VPR: Mechanical (M2), Electrical (E1, E2)
・VMC: Mechanical (25 and 2.50 mill times), Electrical (AC-3) - The VPR of the MS-E provides excellent current isolation performance thanks to combining a vacuum interrupter using spiral contacts manufactured using a new material and an electric control mechanism with a solid track record spanning many years.
3. Operation
- The interior panel drawer-type VPR/VMC/VT units can be moved from the disconnected position (test position) to the operating position without opening the panel (from outside of the panel).
(Drawer-type VPR/VMC units have a mechanical interlock preventing open/close operation during operation and when in an intermediate position.)
4. Safety
- The MS-E design satisfies the internal arc protection classification (IAC) of AFLR.
・The “A” of AFLR restricts access to authorized personnel only, while the “FLR” means safety is required up to a height of two meters in the front (F), sides (L), and rear (R). - MS-E is in the highest operating continuity loss category, securing safety at the time of service and maintenance work, and a protective plate grade (LSC2B-PM class).
- MS-E features mechanical and electro-mechanical interlock conditions complying with IEC62271-200.
5. Maintenance
- To facilitate smooth grounding of the main circuit during service and maintenance work, the grounding switch is located on the main circuit busbar and cable draw-in circuit.
6. Installation
- The MS-E can be transported with the drawer-type VPR/VMC*1 /VT units installed in the panel.
- Sufficient space for cable termination has been secured in the main circuit cable compartment.
- Inter-panel connection of the main circuit horizontal busbar is done by installing a connection conductor.
- Inter-panel connection of the connection conductor is done using the bolts on either side of the connection conductor.
Specification
Standard | IEC 62271-200 |
---|---|
Rated voltage(kV) | 7.2/12 |
Rated frequency(Hz) | 50/60 |
Rated nominal current (A) | 630, 1250, 2000, 3150 |
Rated power freq. voltage(kV) | 20/28-1min |
Rated lightning impulse voltage(kV) | 60/75 |
Rated short-time withstand current (kA) | 25/31.5/40 |
Rated duration of short-time current (sec) | 3 |
Internal Arc Classification | AFLR 40kA/1.0sec |
Dimension WxDxH[mm] (for 630A feeder) | 800 x 2200 x 2600 (*235 for top air vent) |