Factory Automation

Power Management MetersME96SSEB-MB   Specifications

Specifications

Category
Group
Model
Model name
Phase wire system
Rating Current
Voltage
Frequency
Measuring element Current (A) Measuring Item
Class
Current demand (DA) Measuring Item
Class
Voltage (V) Measuring Item
Class
Active power (W) Measuring Item
Class
Reactive power (var) Measuring Item
Class
Apparent power (VA) Measuring Item
Class
Power factor (PF) Measuring Item
Class
Frequency (Hz) Measuring Item
Class
Active energy (Wh) Measuring Item
Class
Reactive energy (varh) Measuring Item
Class
Apparent energy (VAh) Measuring Item
Class
Harmonic current (HI) Measuring Item
Class
Harmonic voltage (HV) Measuring Item
Class
Operating time (h) Measuring Item
Class
Measuring method Instantaneous value
Demand value
Display Display type
Number of display digits or segments Digital section
Display update time interval
Output functions
Input functions
Transmission function Transmission type
Transmission speed
Connection method
Transmission distance
Number of connectable units
Connectable Optional Plug-in Module
Power interruption backup  
VA Consumption Voltage circuit
Current circuit
Auxiliary power circuit
Auxiliary power
Weight
Dimensions
Mounting method
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Electrical Indicators
Electronic Multi-Measuring Instrument
ME96 series
economy model
3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use)
5A AC, 1A AC (common use)
3-phase 4-wire : max 277/480V AC
3-phase 3-wire : (DELTA) max 220V AC, (STAR) max 440V AC
1-phase 3-wire : max 220/440V AC
1-phase 2-wire : (DELTA) max 220V AC, (STAR) max 440V AC
50/60Hz (common use)
A1, A2, A3, AN, AAVG
±0.5%
DA1, DA2, DA3, DAN, DAAVG
±0.5%
V12, V23, V31, VAVG (L-L), V1N, V2N, V3N, VAVG (L-N)
±0.5%
W1, W2, W3, ΣW
±0.5%
var1, var2, var3, Σvar
±0.5%
VA1, VA2, VA3, ΣVA
±0.5%
PF1, PF2, PF3, ΣPF
±0.5%
Hz
±0.2%
Imported, Exported
class 0.5S (IEC62053-22)
Imported lag, Imported lead, Exported lag, Exported lead
class 1S (IEC62053-24)
Imported + Exported
±2.0%
Total
±2.0%
Total
±2.0%
Operating time 1, Operating time 2
(Reference)
A, V: RMS value calculation; W, var, VA, Wh, varh, VAh: Digital multiplication; PF: Power ratio calculation; Hz: Zero-cross; HI, HV: FFT
DA: Thermal type calculation
LCD with LED backlight
First to Third line display: 4 digits, Fourth line display: 6 digits
A, DA, V, W, var, VA, PF: 4 digits; Hz: 3 digits; Wh, varh, VAh: 9 digits (6-digit or 12-digit is also available.); Harmonic distortion ratio/content rate: 4 digits; Harmonic RMS value: 4 digits; Operating time: 6 digits
0.5s, 1s (selectable)
-
-
MODBUS RTU
2400, 4800, 9600, 19200, 38400bps
Multi-drop
1,200m (max)
31 units
Cannot connect optional module
Use of nonvolatile memory (Items: settings, MAX/MIN value, active energy, reactive energy, apparent energy, operating time)
Each phase: 0.1VA (at 110V AC), 0.2VA (at 220V AC), 0.4VA (at 440V AC)
Each phase: 0.1VA (5A AC)
4VA (at 110V AC), 5VA (at 220V AC), 3W (at 100V DC)
100V to 240V AC (±15%), 100V to 240V DC (-30% +15%)
0.3 kg
96 (H) × 96 (W) × 36 (D) mm
Embedded
-5°C to +55°C (Daily average temperature: 35°C or less)
0% to 85% RH, Non condensing
-25°C to +75°C (Daily average temperature: 35°C or less)
0% to 85% RH, Non condensing
  • 先頭 先頭
  • 前 前
  • 最後 最後
  • 次 次

Note1: The class value is a percentage of rated value (100%).

Note2: For harmonics measurement where distortion ratio (content rate) is 100% or more, it can exceed ±2.0%.

Note3: When there is no voltage input, harmonic current cannot be measured.