Factory Automation

MELSEC-F series Input device for temperature sensor

Temperature control blocks support Thermocouple elements and PT100 elements.
FX2N-2LC and FX3U-4LC temperature control blocks are used when the internal PID functions are not precise or fast enough.

Model
(Number of channels)
Available sensor Input specifications Applicable FX PLC
Item Temperature input FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3U-4AD-PT-ADP
(Input 4 ch)
FX3U-4AD-PT-ADP
Platinum resistance thermometer sensor
Pt100, 3-wire
Input
range
-50 to 250°C
Digital output
(-500 to 2500)
*8

Max.
1 unit
*3*4

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 0.1°C
FX3U-4AD-PTW-ADP
(Input 4 ch)
FX3U-4AD-PTW-ADP
Platinum resistance thermometer sensor
Pt100, 3-wire
Input
range
-100 to 600°C
Digital output
(-1000 to 6000)
*8

Max.
1 unit
*3*4

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 0.2 to 0.3°C
FX3U-4AD-TC-ADP
(Input 4 ch)
FX3U-4AD-TC-ADP
Thermocouple
K/J type
Input
range
K type:
-100 to 1000°C
Digital output
(-1000 to 10000)
J type:
-100 to 600°C
Digital output
(-1000 to 6000)
*8

Max.
1 unit
*3*4

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution K type: 0.4°C
J type: 0.3°C
FX2N-8AD
(Input 8 ch)
FX2N-8AD

Discontinued

Thermocouple
K/J/T type
Input
range
K type: -100 to 1200°C
Digital output
(-1000 to 12000)
J type: -100.0 to 600°C
Digital output
(-1000 to 6000)
T type: -100.0 to 350°C
Digital output
(-1000 to 3500)
×

Max.
8 units


Max.
8 units
*9

Max.
8 units
*1*2

Max.
8 units
Resolution [Typical example]
K type: 0.1°C
J type: 0.1°C
T type: 0.1°C
FX2N-2LC
(Input 2 ch)
FX2N-2LC
Platinum resistance thermometer sensor
Pt100, JPt100
Input
range
[Typical example]
Pt100: -200 to 600°C
JPt100: -200 to 500°C
×
Max.
8 units

Max.
8 units
*9

Max.
8 units
*1*2

Max.
8 units
Resolution 0.1°C or 1°C
(differs depending on the sensor used)
Thermocouple
K/J/R/S/E/T/B/N/
JIS C 1602-1995/
PLII/W5Re/W26Re/
U/L type
Input
range
[Typical example]
K type: -100.0 to 1300°C
J type: -100.0 to 800°C
Resolution 0.1°C or 1°C
(differs depending on the sensor used)
FX3U-4LC
(Input 4 ch)
FX3U-4LC
Platinum resistance thermometer sensor
Pt100, JPt100, Pt1000
Input
range
[Typical example]
Pt100: -200 to 600°C
Pt1000: -200.0 to 650.0°C
×

Max.
8 units
*7

Max.
8 units
*9

Max.
8 units
*1*7

Max.
6 units
Resolution 0.1°C or 1°C
(differs depending on the sensor used)
Thermocouple
K/J/R/S/E/T/B/
N/PLII/W5Re/
W26Re/U/L type
Input
range
[Typical example]
K type: -200.0 to 1300°C
J type: -200.0 to 1200°C
Resolution 0.1°C or 1°C
(differs depending on the sensor used)
Low voltage input Input
range
0 to 10 mV DC
0 to 100 mV DC
Resolution 0.5 μV or 5.0 μV
(differs depending on the sensor used)
  • *1When connecting to FX3UC, FX2NC-CNV-IF or FX3UC-1PS-5V is required.
  • *2FX3UC-32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC-**MT/DSS, FX3UC-16MR/D(S)-T: 8 units.
  • *3When connecting to FX3G, FX3G-CNV-ADP is required.
  • *4FX3G 14 pt, 24 pt models: 1 board. 40 pt, 60 pt models: 2 boards.
  • *5For connection to FX3U and FX3UC-32MT-LT(-2), function expansion board is required.
  • *6Supported by FX3UC-32MT-LT ver. 1.30 and later.
  • *7Supported by FX3U and FX3UC ver. 2.20 and later.
  • *8When connecting to FX3S, FX3S-CNV-ADP is required.